Appendix C: PC5020 Commercial Fire
Programming Guide
This section is to be used for programming features related directly to Central and Remote Station Fire Monitoring purposes.
NOTE: The programming as underlined below must be present to successfully satisfy Commercial Fire Installations. For any
Combination Burglary/Commercial Fire Installations; Commercial Fire enable options take precedence over Burglary pro-
gramming options.
[009] PGM1 and PGM2 Output Programming (Main Panel)
PGM 2 must be programmed as type 04 (2-wire smoke support). PGM outputs beyond PGM 4 must not be in Commercial Fire
applications.
Four-wire Smoke Detectors
Zones 1-8 of PC5020 and zones 1-4 on PC5700 may be programmed as 4-wire smoke detectors. To do so enter programming
Option 08 in the desired zone location. Refer to Programming Worksheets Section 3 (Basic Programming ) Section # [001], [002],
[003], [004].
[013] First System Option Code
NOTE: Do not turn this Option ON for Commercial Fire Installations.
[016] Fourth System Option Code
NOTE: For Commercial Fire Applications, this option must be turned ON.
[018] Sixth System Option Code
Default Option ON OFF
NOTE: For Commercial Fire applications this option must be turned ON.
[030] Zone Loop Response Option Code (Optional for Commercial Fire Use)
Fast loop response = Zone response to a violated zone (36ms)
Normal Loop response = Zone response to a violated zone (540ms). Note: All zones are defaulted to this setting.
Refer to Installation Manual: Section 5.3 [030] for description.
[165] Maximum Dialing Attempts for Commercial Fire Applications
Default: 007I ________I________I________IValid entries for maximum dialing attempts must be set in between the range of 005 and 010.
[166] Post Dial Handshake for Commercial Fire Applications
Default: 040I ________I________I________IValid entries for maximum dialing attempts must be set in between the range of 001 and 090.
[177] Waterflow Delay Timer
I ________I________I________IThe maximum time allowed for a waterflow delay time is 120 seconds.
NOTE: This time is to be a combination of both the control unit and the waterflow device.
[178] Alarm Tone Verified for Verbal Alarm
NOTE: This feature is not to be used for Commercial Fire Applications.
[304] Call Waiting String
Default: OFF I________I________I________I This feature must not be enabled for Commercial Fire Applications.
Refer to Section [382] Option 3 from Installation Manual and Programming Worksheets.
[320]-[347],[349] Reporting Codes
NOTE: ALL these reporting codes are defaulted as FF.
Default Option ON OFF
OFF
I________I
1
Normally Closed Loops End of Line Resistors
Default Option ON OFF
OFF
I________I
2
AC Trouble Light Flashes if AC Fails Trouble Light Does Not Follow AC Status
Default Option ON OFF
OFF
I________I
8
AC Trouble Beeps Enabled AC Trouble Beeps Disabled