3.5 Combus Operation and Wiring
The Combus is used by the control panel and the modules to
communicate with each other. The four Combus terminals of the
main panel must be connected to the four Combus terminals or
wires of all modules.
Modules can be home run, connected in a daisy chain or T-
tapped anywhere on the Combus.
The following rules MUST be followed when wiring the Combus:
1. The Combus must be run in minimum 22-gauge wire.
2. No module can be more than 1000' (305m) in cable length
from the main control panel.
3. Shielded wire should only be used in areas that present
excessive RF noise or electromagnetic interference. If shielded
wire is used, the maximum distance a module can be located
from the main panel is significantly reduced. Check the
capacitance limit of the wire to calculate the maximum
distance (see “Capacitance Limits” below).
4. The total capacitance of the Combus wiring must not exceed
80nF (see “Capacitance Limits” below).
Line Loss
When current is drawn through a piece of wire, voltage will be
lost due to the wire’s resistance. This voltage loss must be
considered for all installations.
To ensure proper operation, at least 12.5VDC must be applied to
all modules on the system (when AC is applied and the battery is
fully charged). If less than 12.5VDC is applied, system operation
will be adversely affected.
To correct the problem, try any or all of the following:
1. Connect a PC6204 power supply near the module to provide
power to the Combus.
2. Reduce the length of the Combus run to the module.
3. Increase the gauge of wire.
Capacitance Limits
An increase in capacitance on the Combus will affect data
transmission and will cause the system to slow down.
Capacitance will increase for every foot of wire added to the
Combus. The capacitance rating of the wire used will determine
the maximum length of the Combus.
For example, 22-gauge, non-shielded, 4-conductor wire has a
typical capacitance rating of 20 picofarads per foot (which is
20nF/1000’). For every 1000' of wire added – regardless of
where it is run – the capacitance of the Combus will increase by
20nF.
The following chart indicates the total Combus wire allowed
depending on the capacitance rating of the wire used:
Wire Capacitance per
1000'(300m)
TOTAL Combus Wire
Length
15nF 5300'/1616m
20nF 4000'/1220m
25nF 3200'/976m
30nF 2666'/810m
35nF 2280'/693m
40nF 2000'/608m
Wires run in parallel also increase Combus capacitance. For
example, when using 20nF wire, the following would be some of
the combinations allowed:
Four wire runs at 1000'/305m each
Six wire runs at 666'/203m each
Eight wire runs at 500'/152m each
10 wire runs at 400'/122m each etc…
NOTE: Contact the wire manufacturer for the capacitance
ratings of the wire being used.
3.6 PC6204 Power Supply
PC6204 power supply modules are required to power additional
modules and devices when the total current from the main panel
is insufficient. A PC6204 should also be used if excessive line loss
is encountered.
PC6204 Current Requirement
AUX - 1.5A available for devices connected to the AUX terminal,
including devices connected to relay outputs and modules
connected for Combus repower (see section 3.5 “Combus
Operation and Wiring”).
Combus Repower
Only Relay 1 on the PC6204 can be used for Combus repower.
The Combus must be wired to the PC6204 according to the
following diagram for Combus repower:
IMPORTANT NOTE: Do not use any power supply other than
the PC6204 to repower the Combus. In the event of a power
surge or transient, a module may lock up and cease to
communicate with the control panel. If the panel loses
communication with the module, it will initiate a module
reset and will power down the Combus for five seconds in an
attempt to reset the problem module. After five seconds, the
panel will reapply power to the Combus and the problem
module should begin to operate as intended.
If a power supply other than the PC6204 is used, the Combus
repower function will not operate as intended.