PowerSeries
PC1616/PC1808/PC1832/PC1864 version 4.2 S.Africa
Installation Guide
WARNING: This manual contains information on limitations regarding product use and function and
information on the limitations as to liability the manufacturer. The entire manual should be carefully read.
Przeglądanie stron 0
1 2 3 4 5 6 ... 63 64

Podsumowanie treści

Strona 1 - PowerSeries

PowerSeries PC1616/PC1808/PC1832/PC1864 version 4.2 S.AfricaInstallation GuideWARNING: This manual contains information on limitations regarding produ

Strona 2 - Table of Contents

PowerSeries - PC1616/PC1808/PC1832/PC18648Section 3: ProgrammingThis section provides the information necessary to program all required features for a

Strona 3 - Installation

Section 3: Programming9The Armed and Ready lights indicate programming status:Armed Light ON Panel waiting for 3-digit section numberIf in module prog

Strona 4 - Burglary Zone Wiring Chart

PowerSeries - PC1616/PC1808/PC1832/PC186410Section 4 – Programming DescriptionsThe following is a brief description of the features and options availa

Strona 5 - PC1616/1808/1832/1864

Section 4 – Programming Descriptions11Section [005] System TimesAfter entering Section [005], enter the 2-digit subsection number for the desired part

Strona 6 - DC - 14VDC

PowerSeries - PC1616/PC1808/PC1832/PC186412Section [012] Keypad LockoutThe system can be programmed to ‘lockout’ keypads if a series of incorrect user

Strona 7 - Section 2: User Commands

Section 4 – Programming Descriptions13Section [014] Second System Option CodeSection [015] Third System Option Code[5] ON: auto-arming schedules (Prog

Strona 8 - Master Code all functions

PowerSeries - PC1616/PC1808/PC1832/PC186414Section [016] Fourth System Option CodeSection [017] Fifth System Option CodeSection [018] Sixth System Opt

Strona 9

Section 4 – Programming Descriptions15Section [019] Seventh System Option CodeSection [020] Keypad Zone AssignmentEnter the two-digit zone number to b

Strona 10 - Section 3: Programming

PowerSeries - PC1616/PC1808/PC1832/PC186416Section [023] Tenth System Option CodeSection [030] Fast Loop ResponseThis section is used to determine the

Strona 11

Section 4 – Programming Descriptions17Keypad zones and zone expanders will always follow Section [013].When Zone Types (Section [001] to [004]) are pr

Strona 12

Table of ContentsSection Description Page11.11.21.31.41.51.61.71.81.91.10Installation & Wiring...

Strona 13 - Section [007] Master Code

PowerSeries - PC1616/PC1808/PC1832/PC186418Section [170] PGM Output TimerProgram the time, in seconds, PGM outputs programmed to follow the PGM Output

Strona 14 - Section [012] Keypad Lockout

Section 4 – Programming Descriptions19different format, this account number will be used for all events that are not partition specific (for example,

Strona 15 - ][5] command

PowerSeries - PC1616/PC1808/PC1832/PC186420Section [379] Periodic DLS Time of Day Programs the time the system will auto-call DLS. Program 4 digits –

Strona 16

Section 4 – Programming Descriptions21Section [383] Fourth Communicator Option CodeSection [389] T-Link Fault Check TimerProgram the period of time (i

Strona 17 - ][3] menu access

PowerSeries - PC1616/PC1808/PC1832/PC186422Section [404] Panel Identification CodeProgram the 6-digit Panel Identification Code. This code is used by

Strona 18

Section 4 – Programming Descriptions23PGM Output Option [31]PGM Output Option [32]PGM Output Option [29] and [35]-[41]Section [551] to [564] PGM Parti

Strona 19

PowerSeries - PC1616/PC1808/PC1832/PC186424Section [601] to [608] Additional Reporting Codes Program the reporting code for all events to be transmitt

Strona 20 - ] key press

Section 4 – Programming Descriptions25Section [703] Delay Between Dialing AttemptsProgram the time the panel will wait between dialing attempts to tra

Strona 21

PowerSeries - PC1616/PC1808/PC1832/PC186426Section [904]: Wireless Placement TestEnter Section [904] followed by the 2-digit number of the wireless zo

Strona 22

Section 5: Programming Work Sheets27Section 5: Programming Work Sheets5.1 Index to Programming Work SheetsProgramming Option Page[000] Keypad Enrollme

Strona 23

Section 1: Installation & Wiring1Section 1: Installation & WiringThis Installation Guide provides the basic installation, wiring and programmi

Strona 24

PowerSeries - PC1616/PC1808/PC1832/PC1864285.2 Programming Worksheets Shaded programming sections indicate minimum programming requirements\Keypad Par

Strona 25

5.2 Programming Worksheets29[005] System Times Exit Time Restart shall be disabled when the panel is used in combination with T-Link TL250/TL300. Sec

Strona 26

PowerSeries - PC1616/PC1808/PC1832/PC186430Programmable Output Options01 Residential Burglary and Fire Bell Output 18 Stay Armed Status 36 Zone Foll

Strona 27

5.2 Programming Worksheets31[013] First System Options[014] Second System Options[015] Third System Options[016] Fourth System OptionsOpt Def ON OFF1R

Strona 28

PowerSeries - PC1616/PC1808/PC1832/PC186432[017] Fifth System Options[018] Sixth System Options[019] Seventh System Options Keypad Zone Assignments[02

Strona 29 - Programming Option Page

5.2 Programming Worksheets33[021] Eighth System Options[022] Ninth System Options [023] Tenth System Options[030] Zone Loop Response (Zones 1-8)Opt De

Strona 30 - 5.2 Programming Worksheets

PowerSeries - PC1616/PC1808/PC1832/PC186434[101]-[164] Zone Attributes Zone Attribute Defaults (Y = Option ON; N = Option OFF): Attribute: 123456 789O

Strona 31 - [005] System Times

5.2 Programming Worksheets35Section Zone # Zone Audible/ Steady/ Chime Bypass Force* Swing Tx. Delay Wireless Cross ZnType** Silent Pulsed No No No N

Strona 32 - Other System Options

PowerSeries - PC1616/PC1808/PC1832/PC186436Section Zone # Zone Audible/ Steady/ Chime Bypass Force* Swing Tx. Delay Wireless Cross Zn Type** Silent Pu

Strona 33

5.2 Programming Worksheets37[167] T-LINK Interface Communications Wait for Acknowledge Default 020 I_______I_______I_______I Valid entries are 001-255

Strona 34

PowerSeries - PC1616/PC1808/PC1832/PC186421.1 Keybus WiringThe 4-wire KEYBUS (red, black, yellow and green) is the communication connection between th

Strona 35 - 4][1], [4][2], [4][3]

PowerSeries - PC1616/PC1808/PC1832/PC186438No Activity Arming Timers - Default is [000] for all partitionsSection Partition[191] 1 I_______I_______I_

Strona 36 - [101]-[164] Zone Attributes

5.2 Programming Worksheets39Communications[304] Call Waiting Cancel String (6 Digits) - This feature is activated in Section 382 Opt 4I_______I_______

Strona 37

PowerSeries - PC1616/PC1808/PC1832/PC186440[324]-[327] Alarm Restoral Reporting Codes, Zones 01-64 Section[324] Zone 01 Zone 02 Zone 03 Zone 04 Zone

Strona 38 - System Timers

5.2 Programming Worksheets41[334]-[337] Tamper Restoral Reporting Codes, Zones 01-64 Section[334] Zone 01 Zone 02 Zone 03 Zone 04 Zone 05 Zone 06 Z

Strona 39

PowerSeries - PC1616/PC1808/PC1832/PC186442 [344] Miscellaneous Opening (Disarming) Reporting CodesI_______I_______IFor Future UseI_______I_______IFor

Strona 40

5.2 Programming Worksheets43Call Direction Options[351]-[358] Alarm/Restore Communicator Call Directions [359]-[366] Tamper/Restore Communicator Call

Strona 41

PowerSeries - PC1616/PC1808/PC1832/PC186444[375] System Maintenance Communicator Call Directions [376] System Test Transmissions Communicator Call Dir

Strona 42

5.2 Programming Worksheets45[381] Second Communicator Options[382] Third Communicator Options* A Call Waiting Cancel on a non-Call Waiting line will p

Strona 43

PowerSeries - PC1616/PC1808/PC1832/PC186446[402] DLS Downloading Telephone Number (32 Digits)|____D___|_______|_______|_______|_______|_______|_______

Strona 44

5.2 Programming Worksheets47Section PGM Output 1 2 3 4 5

Strona 45

3PC1616/1808/1832/1864 Wiring DiagramPC Boar d Cabinet Stand Of f Pr imar y:120V A C/60Hz. Secondar y: 16.5VDC 40V A DSCPTD 1640U Class II Tr ansf o

Strona 46

PowerSeries - PC1616/PC1808/PC1832/PC186448PGM Output Partition AssignmentSection PGM Partition: 1 2 3 4 5 6 7 8#Main Board[551] 1 I________I I______

Strona 47

5.2 Programming Worksheets49[605]-[608] Opening (Disarming) Reporting Codes, Access Codes 33-95Section [605] Code 33 Code 34 Code 35 Code 36 Code 37

Strona 48 - Attribute: 12 3 4 5 678

PowerSeries - PC1616/PC1808/PC1832/PC186450INTERNATIONAL PROGRAMMING[700] Automatic Clock Adjust Default = 60 |________|_________| Valid Entr

Strona 49

INTERNATIONAL PROGRAMMING51Module Programming[801] PC5400 Printer Module Programming Refer to the PC5400 Installation Manual for installation and prog

Strona 50 - Extended Reporting Codes

PowerSeries - PC1616/PC1808/PC1832/PC186452For the RecordCustomer: ___________________________________________________________________________________

Strona 51

INTERNATIONAL PROGRAMMING53Zone Programming SummaryZone programming can be found in sections [001] - [004], [101] - [164], [020], [202]-[265]. Use thi

Strona 52

PowerSeries - PC1616/PC1808/PC1832/PC1864Appendix A: Reporting CodesThe following tables contain Contact ID and Automatic SIA format reporting codes.

Strona 53

Appendix A: Reporting Codes[345]-[346] Auxiliary Power Trouble/Rest.Aux voltage supply trouble/restoral MA/R (3) 12 YP-00/YQ-00[345] TLM Failure Telep

Strona 54 - For the Record

PowerSeries - PC1616/PC1808/PC1832/PC1864Appendix B: Troubleshooting GuideTesting:• Power up system• Program options as required (See Programming Sec

Strona 55 - Zone Programming Summary

Appendix B: Troubleshooting GuideTrouble Cause TroubleshootingTrouble [1] Service Required Press [1] to determine specific trou

Strona 56 - Appendix A: Reporting Codes

PowerSeries - PC1616/PC1808/PC1832/PC186441.5 AUX Power WiringThe control panel can provide a maximum of 700mA of current for modules, powered detecto

Strona 57 - Appendix A: Reporting Codes

PowerSeries - PC1616/PC1808/PC1832/PC1864Trouble Cause TroubleshootingTrouble [2] AC FailureNo AC at panel AC input terminalsVerify voltage measured a

Strona 58 - Trouble Summary:

Appendix B: Troubleshooting GuideTrouble Cause TroubleshootingTrouble [5] Zone Fault (Cont.)One or more wireless devices have not checked in within th

Strona 59 - Trouble Cause Troubleshooting

PowerSeries - PC1616/PC1808/PC1832/PC1864Appendix C: Template ProgrammingTemplate programming allows quick programming of the minimum functions requir

Strona 60

Appendix C: Template ProgrammingSelected TroublesOpenings & ClosingsZone Restorals DLS/Installer Lead IN/OUTDigit 5 selects DLS connection options

Strona 61

Note to InstallersThis warning contains vital information. As the only individual in contact with system users, it is yourresponsibility to bring each

Strona 62 - Common Group

Section 2: User Commands5Section 2: User CommandsAny system keypad can be used to program or perform any keypad command. LED keypads use status and zo

Strona 63 - DLS/Installer Lead IN/OUT

PowerSeries - PC1616/PC1808/PC1832/PC18646[][2] Trouble DisplayRefer to Appendix D – Trouble Conditions, for troubleshooting assistance and a detaile

Strona 64 - Note to Installers

Section 2: User Commands7[][6] – User FunctionsPress [][6] followed by the Master Code, then press the number corresponding to the following functio