Section [012] Keypad Lockout
The system can be programmed to ‘lockout’ keypads if a series of incorrect user or installer codes are entered. When lockout is active, all
keypads emit a steady 2-second error tone when a key is pressed. Program the Number of Invalid Codes Before Lockout with the desired
number. Valid entries are from [000] to [255]. Program data [000] to disable the feature. Keypads will remain locked out for the number of
minutes programmed for the Lockout Duration. Valid entries are from [000] to [255].
Section [013] First System Option Code
[20] Command Output 2: Activates when a [][7][2] command is entered on the selected partition – Command can be programmed to require
a valid access code and output can be programmed to activate for the time programmed in Section [170] or programmed to latch.
[21] Command Output 3: Activates when a [][7][3] command is entered on the selected partition – Command can be programmed to require
a valid access code and output can be programmed to activate for the time programmed in Section [170] or programmed to latch.
[22] Command Output 4: Activates when a [][7][4] command is entered on the selected partition – Command can be programmed to require
a valid access code and output can be programmed to activate for the time programmed in Section [170] or programmed to latch.
[23] Silent 24-Hour Input: Changes PGM to a 24-Hour Silent zone (PGM2 only)
[24] Audible 24-Hour Input: Changes PGM to a 24-Hour Audible zone (PGM2 only)
[25] Delayed Fire and Burglary: Functions as a Fire and Burglary output but does not activate until the TX Delay time expires
[26]-[28] For Future Use
[29] Zone Follower: Active when all the selected zones (1-8) are restored and activates when any of the selected zones are violated
[30] Partition Status Alarm Memory: Activates if the selected partition is armed.
Output will pulse “one second ON / one second OFF if an alarm occurs
Option Description
[1] ON: zones require normally-closed loops. OFF: zones require 5.6K End-Of-Line resistors.
[2] ON: zones require double End-Of-Line resistors. OFF: zones require single End-Of-Line resistors.
[3] ON: keypads will display all trouble conditions while armed. OFF: keypads will only display fire trouble when armed.
This option must be OFF if LCD5500 v2.x (or older) keypads are used on the system.
[4] ON: only a trouble will be displayed. OFF: keypads will display a trouble and a zone violation if a tamper or fault is detected.
[5] ON: auto-arming schedules (Program Sections [181]-[188]) will be available to the user in the [][6] menu.
OFF: auto-arming schedules will NOT be available to the user in the [][6] menu.
[6] ON: the Audible Exit Fault feature will be enabled. If a delay zone is not secured correctly and not force-armed, at the end of the exit delay,
the system will go into entry delay and turn ON the bell output. OFF: the keypad will sound the entry delay through the keypad as normal.
[7] ON: the system will NOT log additional alarms for a zone that has reached the swinger shutdown threshold.
OFF: all zone alarms will be logged.
[8] ON: Temporal Three Fire Signal is used to annunciate fire alarms
(½ second ON, ½ second OFF, ½ second ON, ½ second OFF ½ second ON, 1 ½ seconds OFF).
OFF: the system will pulse the bell output
(½ second ON, ½ second OFF).