P R O G R A M D E S C R I P T I O N S
31
[15] Remote Operation (DLS-3 Support)
This output can be activated and deactivated remotely using DLS software.
[16] LINKS1000 Support (PGM1 Only) The output will be used as a data wire to communicate phone number
information for the LINKS1000 cellular unit.
[17] Away Armed The output will activate when the system is armed with the Stay/Away zones activated.
[18] Stay Armed The output will activate when the system is armed with the Stay/Away zones bypassed.
[19] [] [7] [1] Command Output Option #1
[20] [] [7] [2] Command Output Option #2 Press [
]
[7] [2] [Access Code, if required] to activate any output
programmed as one of PGM output option [03], [04] or [20].
Traditionally, [] [7] [2] has been reserved for resetting smoke detectors. Smoke detectors should now be
programmed as output [03] Sensor Reset.
Only ONE of options [03] Sensor ResetOnly ONE of options [03] Sensor Reset
Only ONE of options [03] Sensor ResetOnly ONE of options [03] Sensor Reset
Only ONE of options [03] Sensor Reset
, [04] 2-W, [04] 2-W
, [04] 2-W, [04] 2-W
, [04] 2-W
irir
irir
ir
e Smokee Smoke
e Smokee Smoke
e Smoke
and [20] [ and [20] [
and [20] [ and [20] [
and [20] [
] [7] [2] Command Output Option] [7] [2] Command Output Option
] [7] [2] Command Output Option] [7] [2] Command Output Option
] [7] [2] Command Output Option
#2 may be pr#2 may be pr
#2 may be pr#2 may be pr
#2 may be pr
ogrammed on the same system.ogrammed on the same system.
ogrammed on the same system.ogrammed on the same system.
ogrammed on the same system.
[21] [] [7] [3] Command Output Option #3
[22] [
] [7] [4] Command Output Option #4 These outputs are user-initiated by entering [] [7] [1-4] at any
keypad. When any output is activated, three acknowledgment beeps are heard.
[23] Silent 24 Hour (PGM2 Only) A Panic button may be placed on the PGM2 terminal for use as a silent 24
hour Panic. The keypad will not indicate the alarm in any way and the Bell will remain silent but the PGM2 Alarm
reporting code will be sent to the central station. PGM output option [23] will not activate other programmable
outputs of any kind. This input does not follow Swinger Shutdown.
[24] Audible 24 Hour (PGM2 Only) A Panic button may be placed on the PGM2 Terminal for use as an Audible 24hr
Panic. When the button is pressed, LCD keypads will indicate System in Alarm, the bell will sound until the Bell Cut-off
expires, and the PGM2 Alarm reporting code is sent to the central station. PGM output option [24] will not activate other
programmable outputs except for outputs programmed as [01]. This input does not follow Swinger Shutdown.
[25] Delay Fire and Burglary
This option operates similar to the Fire and Burglary Output (Type 01) except that it will follow the transmission delay
timer programmed in Section [370]. When the timer expires, the output will activate. This is a global output.
Main Board PGM Outputs ...................................... Section [009]
PC5208 PGM Output Options ................................ Section [010]
PC5204 PGM Output Options ................................ Section [011]
5.10.2 Programmable Output Attributes
In addition to programming the output type, you must also program the PGM output attributes for each output.
PGM output options [09] System Trouble and [10] Latched System Event have their own unique set of
attributes listed below the description of each output type.
PGM output options [01], [03]-[08], [11]-[24] have the following attributes:
Attribute ON OFF
[1] Partition 1 controls event Partition 1 Does Not
[2] Partition 2 controls event Partition 2 Does Not
[3] True Output Inverted Output
The output energizes when activated The output will de-energize when activated.
(except for Option [03] Sensor Reset).
[4] 5 Second Pulse Output ON/OFF
The output will activate once for 5 seconds The output will turn ON and OFF when initiated by
(by default) when initiated by the user. the user
(only applicable to options [19] to [22]).
NOTE: The pulse timer can be changed in Programming Section [164]
[5] Access Code Req. No code Req.
The output requires a code for activation. No code required.
(only applicable to keypad-activated outputs)
PGM attributes return to their default settings when you change PGM output options. Please see the
programming worksheets for a list of the default settings for each PGM output type.
Care should be taken in selecting the normal and active states of each PGM output to ensure that an
undesirable output state does not occur after a loss and restore of AC power.
Attribute [2] (ParAttribute [2] (Par
Attribute [2] (ParAttribute [2] (Par
Attribute [2] (Par
tition 2 contrtition 2 contr
tition 2 contrtition 2 contr
tition 2 contr
ols event) is turols event) is tur
ols event) is turols event) is tur
ols event) is tur
ned ofned of
ned ofned of
ned of
f by default for all output options. Attribute [3]f by default for all output options. Attribute [3]
f by default for all output options. Attribute [3]f by default for all output options. Attribute [3]
f by default for all output options. Attribute [3]
must be ON (default) for PGM output options [04], [16], [23] and [24].must be ON (default) for PGM output options [04], [16], [23] and [24].
must be ON (default) for PGM output options [04], [16], [23] and [24].must be ON (default) for PGM output options [04], [16], [23] and [24].
must be ON (default) for PGM output options [04], [16], [23] and [24].
If you program more than one PGM output as the same output type (e.g. If PGM1 and PGM2 are both
programmed as [19] Command Output 1), the settings for output attributes [1], [2] and [5] must be the same.
This does not apply to outputs programmed as types [09] and [10].