39
SIA Format
Level 2 (Hardcoded)
The SIA communication format used in this product follows the level 2 specifications of the SIA Digital Communica-
tion Standard - February 1993. This format will send the Account Code along with its data transmission. At the
receiver, the transmission would look similar to this example:
N Ri01 BA 01
N = New Event
Ri01 = Partition / Area Identifier
BA = Burglary Alarm
01 = Zone 1
PC5016 Reporting Codes SIA Identifiers &
Auto-Reporting Code
Delay Zone Alarm/Restore .................................. BA-XX / BH-XX *
Instant Zone Alarm/ Restore ................................ BA-XX / BH-XX*
Interior Zone Alarm/Restore ................................ BA-XX / BH-XX *
Delay H.A. Zone Alarm/Restore.......................... BA-XX / BH-XX *
Interior H.A. Zone Alarm/Restore ....................... BA-XX / BH-XX *
24 Hr Burg Zone Alarm/ Restore ......................... BA-XX / BH-XX *
Standard Fire Zone Alarm/Restore ...................... FA-XX / FH-XX *
Delayed Fire Zone Alarm/Restore ....................... FA-XX / FH-XX*
24 Hr Supervisory Buzzer Zone Alarm/ Restore .. UA-XX/ UH-XX*
24 Hr Supervisory Zone Alarm/Restore .............. UA-XX / UH-XX *
24 Hr Medical Zone Alarm/ Restore ................... MA-XX / MH-XX *
24 Hr Panic Zone Alarm/Restore ......................... PA-XX / PH-XX*
24 Hr Holdup Zone Alarm/ Restore ..................... HA-XX / HH-XX *
24 Hr Gas Zone Alarm/Restore .......................... GA-XX / GH-XX*
24 Hr Heat Zone Alarm/Restore ......................... KA-XX / KH-XX*
24 Hr Emergency Zone Alarm/Restore .............. QA-XX / QH-XX*
24 Hr Sprinkler Zone Alarm/Restore.................... SA-XX / SH-XX*
24 Hr Water Zone Alarm/Restore ...................... WA-XX / WH-XX*
24 Hr Freeze Zone Alarm/Restore ....................... ZA-XX / ZH-XX*
24 Hr Latching Tamper Alarm/Restore .............. BA-XX / BH-XX *
Duress Alarm .......................................................................HA-00
Opening After Alarm .......................................................... OR-00
Recent Closing .................................................................... CR-00
Zone Expander Supervisory Alarm/Restore .......... UA-00/UH-00
Keypad Fire Alarm/Restore................................... FA-00 / FH-00
Keypad Auxiliary Alarm/Restore ......................... MA-00 / MH-00
Keypad Panic Alarm/Restore ............................... PA-00 / PH-00
2-Wire Smoke Alarm/Restore ................................ FA-00 / FH-00
Appendix B
SIAVFORMAT
PC5016 Reporting Codes SIA Identifiers &
Auto-Reporting Code
Zone Tamper (1-32) ............................................................ TA-XX *
Zone Tamper Restorals (1-32) ........................................... TR-XX*
General System Tamper/ Restore ......................... TA-00 / TR-00
Keypad Lockout .................................................................. JA-00
Closing By Access Codes 1-32, 33, 34, 40-42.................. CL-XX
Partial Closing .................................................................... CG-XX
Special Closing (DLS, Keys, Maint, Quick)........................ CL-00
Opening By Access Codes 1-32, 33, 34, 40-42 ............... OP-XX
Auto-Arm Cancellation ........................................................ CE-00
Special Opening (DLS, Keys, Maint) ................................. OP-00
Battery Trouble Alarm/ Restore .............................. YT-00/YR-00
AC Failure Trouble Alarm/ Restore ......................... AT-00/AR-00
Bell Circuit Trouble Alarm/Restore ........................ UT-99/ UJ-99
Fire Trouble Alarm/Restore ..................................... FT-00 /FJ-00
Auxiliary Power Supply Trouble Alarm/Restore .... YP-00 / YQ-00
TLM Trouble Code (via LINKS) ........................................... LT-00
General System Trouble/ Restore ........................... YX-00/YZ-00
General System Supervisory/ Restore .................... ET-00/ER-00
TLM Restoral ....................................................................... LR-00
FTC Restoral ........................................................................ YK-00
Event Buffer 75% Full Since Last Upload ........................... JL-00
DLS Lead In......................................................................... RB-00
DLS Lead Out (Successful) ................................................ RS-00
Periodic Test Transmission................................................. RP-00
System Test ......................................................................... RX-00
LINKS1000 Test Transmission Code ................................. TX-00
General Transmitter Low Battery/Restore ............. XT-00/XR-00
General Zone Trouble/ Restore .............................. UT-00/UJ-00
* Zone Number is Identified
User Number is Identified
Each Zone Number is Identified (using UB-XX)