P R O G R A M D E S C R I P T I O N S
30
8 low current outputs available with the PC5208 Output Module
4 high current outputs available with the PC5204 Power Supply/Output Module
Programming any of the PGM Outputs is a two step process. First an option from the below list must be selected for
the PGM Output. Second the PGM Attributes must be selected. The following is a list of the PGM Output Options
and PGM Attributes.
5.10.1 PGM Output Options
[01] Burglary and Fire Bell Output The PGM output will activate when the alarm output is active and will turn
off when the alarm output is silenced. If the alarm output is pulsing the PGM output will pulse as well. This output
will follow the activation of the alarm output (pre-alert) for delayed fire zones.
[02] for future use
[03] Sensor Reset ([] [7] [2])
This output will normally be active (switched to ground).
This option is used to reset power for latching smoke detectors. The output will deactivate for five seconds when
the [
] [7] [2] command is entered (see Section 3.4 [] [7] Output Functions). The keypad buzzer will not
sound for the five second period.
Please refer to the Control Panel Wiring Diagram in this manual for wiring instructions.
Only ONE of options [03] Sensor Reset, [04] 2-Wire Smoke and [20] [
] [7] [2] Command Output
Option #2 may be programmed on the same system.
[04] Two-Wire Smoke Support (PGM2 Only) PGM2 may be used in conjunction with two-wire smoke detectors.
PGM Output Attributes for PGM2 when used for two wire smoke detector support must remain at
default, Attribute 1, 2 and 3 ON.
Do not program any PGM output other than PGM2 for two-wire smoke detector support.
Refer to the Hook-Up diagram in this manual for wiring instructions
(See Section 2.9.5 Fire Zone Wiring - 2-Wire
Smoke Detectors)
.
[05] Partition/System Armed Status The PGM output will activate when the Partition or System is armed and
deactivate when disarmed.
[06] Ready Output The PGM output will activate when the Partition or System is ready to arm. The output will
deactivate when the system is not secure or upon arming.
[07] Keypad Buzzer Follow The PGM will activate when any of the following events occur and will remain
active for as long as the keypad buzzer is active:
Door Chime Entry Delay Audible Exit Delay
Auto-Arm Prealert 24 Hour Supervisory Buzzer Zone
[08] Courtesy Pulse Upon arming the PGM output will activate for the duration of the exit delay plus two
minutes. Upon entry the PGM output will activate for the duration of the entry delay plus two minutes. Only one
courtesy pulse output may be programmed on a system.
[09] System Trouble Output The PGM output will activate when any of the selected trouble conditions are
present. It will deactivate when all the selected trouble conditions are cleared.
The PGM attributes for this option, programmed in Sections [141] to [142], differ from the standard selection of
attributes. Program which trouble conditions will activate the output by selecting some or all of the following
attributes:
[1] .. Service Required [3] .. Telephone Line Trouble [6] .. Zone Tamper
(battery, bell, general trouble, [4] .. Failure to Communicate [7] .. Zone Low Battery
general tamper, general supervisory) [5] .. Fire Trouble / Zone Fault [8] .. Loss of Clock
[2] .. AC Failure
[10] Latched System Event (Strobe Output) The output will activate when any of the selected system events
(alarms) occur on the system. In the armed state, the output will deactivate only once the system is disarmed.
If an alarm activates this output in the disarmed state, the output will deactivate if a user enters a valid access
code while the Bell Cut-off timer is counting down. The output will also deactivate if someone arms the system
after the Bell Cut-off has expired. This output can be used to indicate that an alarm has occurred before entering
the premises.
The PGM attributes for this option, programmed in Sections [141] to [154], differ from the standard selection of
attributes. Program which events will activate the output by selecting some or all of the following attributes:
[1] ...... Burglary (Delay, Instant, Interior, Stay/Away and 24 Hour Burglary Zones)
[2] ...... Fire (Fire Keys, Fire Zones)
[3] ...... Panic (Panic Keys and Panic Zones)
[4] ...... Medical (Auxiliary Keys, Medical and Emergency Zones)
[5] ...... Supervisory (Supervisory, Freezer and Water Zones)
[6] ...... Priority (Gas, Heat, Sprinkler and 24 Hour Latching Zones)
[7] ...... Holdup (Holdup zones)
This output will activate for silent and audible alarms or medical conditions only. It will not activate
during pre-alert or delays.