P R O G R A M D E S C R I P T I O N S
38
5.32.1 Factory Default Main Panel (Hardware)
Step 1 - Remove AC and battery from the panel.
Step 2 - Remove all wires from the Zone 1 and PGM1 terminals.
Step 3 - With a piece of wire short the Zone 1 terminal to the PGM1 terminal.
Step 4 - Apply AC power to the main panel.
Step 5 - When Zone Light 1 is lit on the keypad the default is complete.
Step 6 - Remove AC power from the control
Step 7 - Reconnect all original wiring and power up the control.
AC power must be used to power the panel. The panel will not default if the battery is used.
5.32.2 Factory Default Main Panel (Software) and other Modules
Step 1 - Enter the Installer Programming mode. Step 3 - Enter the Installer Code.
Step 2 - Enter Program Section [XXX]. Step 4 - Enter Program Section [XXX] again.
The panel will take a few seconds to perform the default. When the keypad is again operational the default is complete.
Restore LINKS2X50 & Skyroute to Factory Default Programming ... Section [993]
Restore PC5100 to Factory Default Programming ............................. Section [994]
Restore Escort5580 to Factory Default Programming ....................... Section [995]
Restore PC5132 to Factory Default Programming ............................. Section [996]
Restore PC5400 to Factory Default Programming ............................. Section [997]
Restore PC5928/PC5936 to Factory Default Programming .............. Section [998]
Restore Main Panel (Software) to Factory Default Programming ..... Section [999]
5.33 Installer Lockout
If Installer Lockout is selected a hardware default cannot be performed. If a software default is performed all
programming will restore to factory default.
When Installer Lockout Disable is selected the panel will restore all programming to factory defaults if a
hardware or software default is performed on the main control panel.
To enable or disable Installer Lockout perform the following:
Step 1 - Enter Installer Programming. Step 3 - Enter the Installer Code.
Step 2 - Enter Program Section [XXX]. Step 4 - Enter Program Section [XXX] again.
Installer Lockout Enable ........................................ Section [990]
Installer Lockout Disable ....................................... Section [991]
5.34 Walk Test (Installer)
The Installer Walk Test can be used to test the alarm state of each zone of the panel. The walk test cannot be
used to test zone type [24].
Before beginning the walk test, ensure the following conditions are met:
1. The panel is disarmed
2. The Keypad Blanking option is disabled (section [016]: [3])
3. The Fire Bell is Continuous option is disabled (section [014]: [8])
4. The Transmission Delay is disabled, if Transmission Delay is not required (section [370])
Fire Troubles are not supported in Walk Test.
To perform a Walk Test, do the following:
Step 1 - Enter Installer Programming
Step 2 - Enter Section [901]
When any zone is violated the panel will activate the Bell Output for two seconds, log the event to the Event
Buffer and communicate the alarm to central station. Each zone should be tested several times during the test.
Check the event buffer to ensure that all zones and FAP keys are functioning properly.
To stop the test, you must do the following:
Step 1 - Enter Installer Programming
Step 2 - Enter Section [901]
Check the Event Buffer after the Walk Test is complete, to ensure that the Audible/Silent 24-hr PGM alarms have
been restored.
The Alarm Memory is cleared upon entering Walk Test mode. When the Walk Test is complete, the
Alarm Memory light will remain lit, but there will be no alarms in memory. The light will turn off the
next time the panel is armed.